STRUCTURE DESIGN
REQUIREMENTS
The design of piles and foundations shall be
based on the soil investigation carried out by the Contractor and on the
preliminary loading tests performed at site as specified in the Technical
Specification.
Unless otherwise required by manufacturer’s
equipment specifications, the total settlement of structures shall not exceed 3
cm.
The supporting structural steel for all
buildings and structures furnished by the Contractor shall be adequate
strength, stiffness and rigid and shall be adequately braced for the loads to
which the steel will be subjected, and shall be completely suitable for the
service.
All steel structures shall be designed by the
working stress method, and all reinforced concrete structures shall be designed
by the ultimate strength method, based on the latest edition of the AISC and
ACI-318 Codes respectively.
The design shall conform to applicable
requirements of the codes and standards referenced in clause above.
All Contractor’s designs, detailing and shop drawings shall be approved by the Owner before fabrication and construction.
DESIGN LOADINGS
The design of the civil works shall take account
of all loads applied including Dead, Imposed, Wind, Thermal, Dynamic,
Settlement, Movement, Seismic and other loading, condition where appropriate.
Temporary load during testing, maintenance and erection shall also be
considered.
The standards used and loading assumptions made
shall be stated in the design basis and calculations.
LOADING CRITERIA
All structural components shall be designed for
the following minimum loads:
Dead Loads
The dead loads consist of structure and
equipment of a permanent and semi permanent nature.
The load includes the weight of framing, roofs,
floors, walls, partitions, platforms, and all permanent equipment and
materials.
The vertical and lateral pressures of liquids
shall also be treated as dead loads.
Live Loads
Live loads consist of assumed unit loadings
deemed sufficient to provide for movable or transitory loads such as people,
portable equipment, fixture and parts lay down.
Live loads used for design shall not be less
than those listed below. Other design loads are described separately in another
section.
Live Loads
The following minimum live load shall be used
into the design:
General:
Roofs 150 kg/m2
Offices 400 kg/m2
Assembly and locker
rooms 500 kg/m2
Laboratories 500 kg/m²
Stairs and walkways 500 kg/m2
Platform & gratings 500 kg/m2
Ground floors 1250
kg/m2
Surcharge adjacent to
plant structures 1250 kg/m2
Load at top of any
handrail on any direction 100 kg
Power Building:
Turbine Bay operating
floor 1250 kg/m2
Auxiliary Bay operating
floor 1000 kg/m2
Turbine Lay-down area 2500 kg/m2
Mezzanine 750
kg/m²
Control room 1000 kg/m2
Switchgear floor
1000 kg/m²
Cable room 750
kg/m2
Battery room 1250 kg/m2
Coal conveyor Gallery,
Tripper area or
Surcharge adjacent to
plant structures -
Transfer House 1250 kg/m2
Steel grating 750
kg/m2
Notes:
a.1 Equipment loads shall be
considered when designing floors. Live loads given shall not be superimposed
over the areas occupied by the equipment unless there is space for possible
storage or traffic under the equipment.
a.2 The floors shall be
designed for the removal of equipment as required per the equipment removal
arrangement.
a.3 Interior partition wall
loads shall be considered when designing floors.
Pipe Hanger Loads
Piping loads for main steam, boiler feed,
condensate, and extraction lines shall be specifically determined and located.
Piping expansion loads and dynamic load shall be
considered on an individual design basis. Loads imposed on perimeter beams
around pipe chase areas will also be specifically determined.
Pipe dead loads for other areas shall be
determined as uniform loads per square meter of floor area and shall be carried
to columns and foundations as pipe dead loads.
Impact Loads
The following minimum impact factors shall be
used in addition to other loads for components supporting reciprocating or
rotating machines, hoist, cranes, or other equipment creating dynamic forces;
unless the Contractor uses larger values:
·
For
supports of elevators 100 %
·
For
cab-operated traveling crane support girders and their
connections 25 %
·
For
pendant-operated traveling crane support girders and
their connections 10 %
·
For
supports of light machinery, shaft or motor driven 20 %
·
For
supports of reciprocating machinery or power driven units 50
%
·
For
hangers supporting floors and balconies 33 %
Construction Loads
All structural components shall be designed for
anticipated loadings imposed by construction.
Appropriate areas of the ground floor slabs of
the power plant buildings and adjacent underground utilities shall be designed
to support the operating loads of large construction cranes. The steel framing
system shall be designed for stability at all stages of erection.
Wind Load
Minimum loads shall be based on wind velocity of
2 knots or wind stagnation pressure of 60 kg/m², adjusted for height above
ground, shape factor and other requirements in accordance with American
National Standards Institute (ANSI) A 58.1.
The stack shall be designed by taking into
account to oscillation due to wind pressure.
Seismic Load
The seismic load shall be zone 1 accordance the latest Indonesian earthquake
standard published by Ministry of Pemukiman & Prasarana Wilayah.
Crane Load
Crane lateral forces shall be determined in
accordance with the requirement of AISC.
Lane Load
The minimum truck and lane loading shall be the
AASHTO HS-20-44 loading.
Abnormal Load
This load shall include loads by postulated
accident condition such as emergency torque of generator, and other loads as
given by equipment manufactures.
Loading Combination
The load combination for reinforced concrete
structure with ultimate strength design as shown on the Table 4.4.3 – 1.
The load combination for steel structure with
elastic design is shown on the Table 4.4.3 – 2.
TABLE
Part 4.4.3 - 1
|
||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
LOAD COMBINATION
FOR REINFORCED CONCRETE
|
||||||||||||||||||||||||||||||
STRUCTURE WITH ULTIMATE STRENGTH DESIGN |
||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
||||||||||||||||||||||||||||
|
|
LOAD
|
||||||||||||||||||||||||||||
|
|
|
|
|
||||||||||||||||||||||||||
LOADING
CONDITION
|
NO.
|
NORMAL
|
SEVERE
|
DESIGN
|
||||||||||||||||||||||||||
|
|
|
ENVIRONMENTAL
|
STRENGTH
|
||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
D
|
Dd
|
L
|
Ln
|
T0
|
R0
|
C
|
P0
|
M0
|
E
|
W
|
H
|
Wv
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
Construction
|
1
|
1.1
|
|
1.3
|
1.1
|
|
1.1
|
1.3
|
|
1.3
|
|
1.3
|
|
|
ACI 318
|
|||||||||||||||
|
2
|
|
0.9
|
|
1.1
|
|
|
1.3
|
|
1.3
|
1.3
|
|
ACI 318
|
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
Test
|
3
|
1.1
|
|
1.3
|
1.1
|
1.3
|
1.4
|
1.3
|
1.3
|
1.3
|
|
ACI 318
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
Normal
|
4
|
1.4
|
|
1.7
|
1.4
|
1.7
|
1.4
|
1.7
|
1.7
|
1.7
|
|
ACI 318
|
||||||||||||||||||
|
5
|
0.9
|
|
|
1.4
|
|
0.9
|
|
|
|
|
ACI 318
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
Severe
|
6
|
1.1
|
|
1.3
|
1.1
|
1.3
|
1.1
|
1.3
|
1.3
|
1.3
|
1.4
|
|
|
0.5
|
ACI 318
|
|||||||||||||||
|
7
|
0.9
|
|
|
1.1
|
1.3
|
1.1
|
1.3
|
1.3
|
1.3
|
1.4
|
|
|
0.5
|
ACI 318
|
|||||||||||||||
|
8
|
1.1
|
|
1.3
|
1.1
|
1.3
|
1.1
|
1.3
|
1.3
|
1.3
|
|
1.3
|
|
0.9
|
ACI 318
|
|||||||||||||||
|
9
|
0.9
|
|
|
1.1
|
1.3
|
1.1
|
1.3
|
1.3
|
1.3
|
|
1.3
|
|
0.9
|
ACI 318
|
|||||||||||||||
|
10
|
1.1
|
|
1.3
|
1.1
|
1.3
|
1.1
|
1.3
|
1.3
|
1.3
|
|
|
1.3
|
1.3
|
ACI 318
|
|||||||||||||||
|
11
|
0.9
|
|
|
1.1
|
1.3
|
1.1
|
1.3
|
1.3
|
1.3
|
|
|
1.3
|
1.3
|
ACI 318
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
TABLE Part 4.4.3 - 2 |
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LOAD COMBINATION
FOR STEEL STRUCTURE
|
|||||||||||||||
WITH ELASTIC
DESIGN
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
LOAD
|
|||||||||||||
|
|
|
|
|
|||||||||||
LOADING CONDITION
|
NO.
|
NORMAL
|
SEVERE
|
DESIGN
|
|||||||||||
|
|
|
ENVIRONMENTAL
|
STRENGTH
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
D
|
Dd
|
L
|
Ln
|
T0
|
R0
|
C
|
P0
|
M0
|
E
|
W
|
H
|
Wv
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Construction
|
1
|
1.0
|
|
1.0
|
|
1.0
|
1.0
|
1.0
|
|
1.0
|
|
|
1.33 AISC
|
||
|
2
|
1.0
|
|
1.0
|
|
|
1.0
|
1.0
|
|
1.0
|
1.0
|
|
1.33 AISC
|
||
|
3
|
|
0.75
|
|
|
|
|
1.0
|
|
1.0
|
1.0
|
|
1.33 AISC
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Test
|
4
|
1.0
|
|
1.0
|
1.0
|
1.0
|
1.0
|
1.0
|
1.0
|
1.0
|
|
1.33 AISC
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Normal
|
5
|
1.0
|
|
1.0
|
|
1.0
|
1.0
|
1.0
|
1.0
|
1.0
|
|
1.00 AISC
|
|||
|
6
|
1.0
|
|
1.0
|
1.0
|
1.0
|
1.0
|
1.0
|
1.0
|
1.0
|
|
1.33 AISC
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Severe
|
7
|
1
|
|
1.0
|
1.0
|
|
1.0
|
1.0
|
1.0
|
1.0
|
1.0
|
|
|
0.33
|
1.33 AISC
|
|
8
|
0.75
|
|
|
1.0
|
|
1.0
|
1.0
|
|
1.0
|
1.0
|
|
|
0.33
|
1.33 AISC
|
|
9
|
1
|
|
1.0
|
1.0
|
|
1.0
|
1.0
|
1.0
|
1.0
|
|
1.0
|
|
0.75
|
1.33 AISC
|
|
10
|
0.75
|
|
|
1.0
|
|
1.0
|
1.0
|
|
1.0
|
|
1.0
|
|
0.75
|
1.33 AISC
|
|
11
|
1
|
|
1.0
|
1.0
|
|
1.0
|
1.0
|
1.0
|
1.0
|
|
|
1.0
|
1.0
|
1.33 AISC
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note: Load
Definitions
A.
Normal
Loads
D - Dead
Load - This includes self-weight of structure, waterproofing,
insulation, fireproofing, siding,
partitions, equipment, mechanical and electrical components, etc.
Dd is minimum Dead Load
C
- Crane Load – Crane and trolley loads including
lift load, weight of trolley
and bridge and
their impact.
L
- Live Load - This includes loads that vary in
magnitude such as occupancy load, moving vehicle load, etc.
Ln is
minimum occupancy Live Load during test, seismic and severe
environmental
event.
Po
- Pressure Load - Internal pressures at
normal operating condition.
Ro
- Reaction - Normal-operating reactions of
piping, duct and cable trays at
support or anchor points.
To - Temperature loads - Most critical transient or steady state thermal
loads
condition on the structure at
normal operating or shutdown condition.
This also includes other
thermal effects such as frictional loads due to
expansion.
Mo - Other miscellaneous loads such as the high voltage line pull - off
loads,
belt pull loads, and vehicle
loads etc.
B.
Severe
Environmental Loads
E - Seismic Load
W - Wind Load
H - Hydrostatic Load
WV - Wave Load
DETAIL
DESIGN REQUIREMENT
Foundation Design
The pile length shall be
based on the soil investigation result and loaded tests of piles.
A minimum safety factor
shall be provided as shown below:
- Overturning 1.50
- Slidding 1.10
- Bouyancy 1.25
In general the
foundation design should ensure that:
The machine can be
operated efficiently and reliably without undue or excessive wear. Foundation
dynamic analysis shall be submitted for approval.
The foundation itself
suffers no damage or settlement sufficient to cause the machine to function in
efficiency or to require realignment.
The waves propagated
through the soil by vibration of the foundation should not be harmful to persons
or to adjacent structures, sensitive machinery or processed.
The foundation adapted
is the most economical which will meet all the necessary requirements.
The seasonal variations
in the ground water table level and the effect of such variations shall be
taken into account on the foundation characteristic.
Concrete Design
Individual foundations
of a building shall be interconnected in two directions generally at right
angles by members designed for an axial tension and compression equal to 10 %
of the maximum vertical load on either-foundation under seismic conditions.
If the axial load in one
of the interconnected columns is less than 20 % of that in the other column,
the design axial load shall be taken as 10 % of the average vertical load on
the two foundations under seismic conditions.
Steel Structure Design
All structure shall be
designed to support the above imported loads.
Design, detail,
construction and erection of structural steel shall conform to the requirements
of AISC or other International code but should be similar or better than AISC
code.
The depth of fully
stressed beams and girders shall not be less than Fy/56000 (Fy in kg/cm2)
times span unless allowable stresses are reduced. The corresponding maximum L/D
ratio for A36 shall be 22 for simply supported members. The L/D ratio not
exceeds 30 under any circumstances.
For cantilevered beams,
the maximum L/D ratio shall not exceed 5.
For strut members, i.e.
members subjected to axial load and bending due to self-weight only, the L/D
ratio shall not exceed 22.
For flexural members
supporting reciprocating or rotating machinery, the maximum L/D ratio shall be
12.
The deflection of beams,
girders under normal load shall not exceed 40 mm or L/300 whichever is less.
The deflection of plate
girders or vertical trusses supporting columns or heavily loaded posts shall be
limited to L/1000 but not to exceed 20 mm.
All connections shall be
shop welded and field bolted and shall conform as a minimum to AISC Manual
Table II (bolt) and Table III (weld) unless noted otherwise. Special
connections shall be designed by Contractor for connections having large
shears, axial forces, moments and copes.
The maximum slenderness
ratio (KL/r) of the steel columns shall be limited to 200.
The steel lateral
load-resisting system shall be analyzed and designed to function independently
from shear-resisting concrete or concrete masonry exterior and interior walls,
and concrete floor slabs acting as shear-resisting diaphragms.
The lateral deflection
or drift of a story relative to its adjacent stories due to seismic event shall
not exceed 0.005 Hsx as defined in the UBC. Hsx is the story height of the
vertical bracing panel.
The maximum drift due to
wind load shall be limited to 0.002H, where H is the building height below the
level under consideration.
The bracing system
should be laid out with regard to permanent and temporary access requirements
for equipment removal purposes.
The horizontal
deflection of girt due to wind load shall be limited to 1/180 of the span. For
girt supporting windows, the allowable horizontal and vertical deflections
shall be consistent with the manufacturers’ requirement (typically 6 mm for
glass windows). The vertical deflection of the carrier beam shall be limited to
the lesser of 25 mm or 1/300 of the span.
The minimum access
gallery width shall be 75 cm unless noted otherwise. A minimum headroom
clearance of 2.1 m shall be maintained over all galleries. All gratings shall
be galvanized and suitable for the outdoor environment.
Grating, checkered plate
or metal deck shall not be considered as lateral support for the floor beam.
The column base plates
and shear bars shall be designed so that the bearing stresses on concrete
foundations do not exceed the allowable value for 225 kg/cm2
concrete in 28 days.
All column base plates
shall be founded on concrete foundations at grade level unless otherwise noted.
ARCHITECTURAL DESIGN REQUIREMENT
Floor
An additional topping
slab over the structural concrete slab shall be used where switchgear is to be
installed or where specifically required for setting of Contractor’s equipment.
Ceramic tile floor
finish shall be used in the building areas such as, the offices, the meeting
rooms, the kitchens, the hall ways, the stairs, and other areas indicated on
the Bid drawings.
Raised floor/elevated
floor shall be used in the computer and control rooms for encase equipment
drains and conduits.
Glazed tiles shall be
used for the toilets, locker and shower rooms.
The battery room floor
and wall shall be coated with epoxy coating. The epoxy shall have chemical
resistance to alkalis acids solvents, and beverages with the material density
and bonding strength of not less than 1.3 kg/cm3 and 25 kg/cm2
respectively.
Metal Siding & Metal
Deck Roofing
The metal siding and
metal roof decks for the building shall be in accordance with technical
specification.
Insulated metal siding
and insulated metal roof shall be provided at least for the steam turbine
buildings, control building, and others building as required, and shall be
designed to obtain thermal and noise reduction in accordance with the above
referenced specification.
The color of metal
siding and roof deck shall be as specified in the Bid drawings or as selected
by the Owner after award of this contract with no additional cost to the Owner.
All gutters shall be
galvanized steel, similarly coated and colored to match the siding.
All metal siding and
roof shall be designed weather, water and dust tight.
The metal deck roof
pitches shall be minimum of 50 with respect to horizontal plane. All
roof water shall be collected at edge gutters and down spouts and discharged on
the concrete splash blocks at grade.
Exterior and Interior Masonry Walls
Exterior Walls
Walls for the building,
shall be made of Hollow concrete block masonry wall. The wall shall be
plastered and coated finished on both side surfaces.
All complete exterior
walls shall weather, and dust tight.
Interior Walls
Hollow concrete block
masonry which is plaster and coated finished on both side surface shall be
provided for the interior walls.
Doors
Wooden doors with
aluminum frame shall be used for the office, the toilet rooms and the light
duty interior door applications.
Steel doors and aluminum
frame shall be used in other buildings based on Owner’s approval.
Single doors shall be
minimum 0.80 m wide and 2.10 m high. Where double doors are required they shall
be sized with consideration for equipment removal.
Doors more than 2 m wide
shall be electric operated steel rolling doors.
Vision panels of the
doors shall be clear polished wire glass.
The doors located in the
control shall be sound proof and shall have a minimum sound transmission class
rating of 40 decibels.
All normally opening
door leaves shall be fitted with heavy duty type door closers.
The Contractor shall
submit shop drawings to the Owner for approval before fabrication.
Windows
Windows shall be
anodized aluminum with clear polished glass except in the turbine building
where wire reinforced glass shall be used.
Windows provided in the
control room shall be insulated glass or double glass in order to obtain noise
and thermal insulation.
Louvers
Louvers shall be used in
the equipment rooms and other areas for ventilation purposes.
Louvers shall be anodized
aluminum louvers and at exterior locations shall be provided with the insect
screen.
Ceilings
The layout of suspended
ceilings shall be made with close coordination with the ventilation, the air
conditioning and the lighting requirements.
Suspended acoustic tile
ceiling shall be provided in the office areas, the computer room, the
laboratory, etc.
Suspended moisture
resistant acoustic tile ceiling shall be provided in the toilets, the locker
and the shower rooms and kitchen.
Stairs
Steel stairs shall be
used in general plant area where it is use for service of equipment or to
travel from one gallery level to another.
Ladders
Ladders shall be
provided in all pits, manholes, to all roof over 6 m above the ground where
there is no access by a stair on to the floor and the equipment galleries where
no stair system is provided.
Hand Rails
Hand rails shall be
provided for the following area :
·
Around
every stairway floor opening
·
Around
every floor opening into which a person can walk
·
Every
open-sided floor, walkways and platforms
·
Adjacent
to dangerous equipment
OTHER
CIVIL DESIGN REQUIREMENT
Roads
CBR test on the finished
level of sub grade shall be held to a maximum value of 8 with 6 is preferable.
Minimum radius of
curvature shall be 15 m.
Unless otherwise noted
on the Bid drawing the main road width shall be 8 m with 1.5 m shoulder, other
roads shall be 6.00 m with 1.0 m shoulder.
Loading over culverts
and pipes shall be in accordance will AAHSTO HS20-44 except for areas subject
to loading by the special heavy haul vehicles.
The Contractor shall
provide additional traffic signs along the new road in the Power Plant as
directed by the Owner.
Storm Drainage
The Contractor shall
design and provide the drainage system but not limited to as specified in the
Technical Specification and as shown on the Bid drawing.
For the storm drainage
system, the ditches and the culvert shall be adequate to discharge surface run
off due to a 10 years recurrence interval storm.
The minimum size of
culverts shall be 300 mm wide and the culverts shall be made of reinforced
concrete. The culvert shall be designed for a maximum velocity of 2.5 m/sec.
The storm sewer shall be
provided with adequate number of manholes with heavy-duty frame and covers.
Minimum diameter of
manholes shall be 1000 mm and manholes shall be installed at the changes in
grade, size or alignment, at all intersections and interval, not greater than
100 m.
The ditches shall be of
reinforced concrete and minimum slope as directed by the Owner.
Transformer Area
Drainage & Oil Separator
To
contain accidental oil spills, all drainage from the transformer area and
Diesel fuel-unloading facility shall be routed through an oil separator.
The
design of transformer pit and piping from the transformer pit to oil separator
shall be based on the largest flow expected from the following condition unless
Contractor requires larger.
Surface
run-off shall consider 10 years recurrence interval from the transformer area.
Deluge
system flow for the largest transformer fire protection system-estimated flow
rate 30 liters/s.
Accidental
oil spills from the largest transformer-estimated spilled oil volume of 3000
liters unless the Contractor requires larger.
The
size of the main line connecting to the oil separator shall be sized to handle
additional flow from other area as required.
Sanitary Waste Water
The Contractor shall
design and provide the septic tank and shall be reinforced concrete with
manholes and baffle.
The septic tank with
drainage system shall have a sufficient capacity for accommodation of the
minimum 50 person for the facilities of the control building, the water
treatment plant, and the substation building.
Drainage from the mess
room and toilet area of building above shall be routed to the septic tank
before discharged to the wastewater storage pond.
The elevated piping from
the building to the ground level and piping to the waste water storage pond
shall be cast iron and under ground piping to septic tank shall be PVC pipe
with the minimum size of 150 mm diameter.
Clean out shall be
provided at every 30 m and each change in direction of the sewer system.
Prior to the design of
the tile drainage absorption field, Contractor shall perform percolation tests
to determine the absorption rate. Based on the field percolation test results
the size of the absorption field shall be determined.
Plant Water
Drainage system from the
plant water shall be discharge to the wastewater storage pond.
Piping material can be
cast iron, PVC or GRP according to the requirement.
Shelter
The shelter shall be
provided for, but not limited to the following equipment/plant:
a. Demin Pump
b. Service Water Pump
c. Other structures as
directed by the owner
The shelter shall be
designed with steel structure and provided with metal roofing. Floor shall be
designed with reinforced concrete slab.
Oil Pipe and Cable
Bridge
Oil pipe and Cable
Bridge shall be steel structure pipe sleepers and bridge abutments shall be
reinforced concrete founded on prestressed concrete pile.
Chemical Resistant
Lining
All water and the
wastewater concrete tanks and ponds shall be lined with epoxy coating with
fiberglass fabric reinforcements suitable for the chemistry of the effluent.