DESIGN AND FABRICATION OF STRUCTURAL STEEL


SCOPE OF WORK

The scope of work shall be in accordance with BOOK II Subsection "Summary Scope of Work" and Book III A refers to "General Civil and Architectural Design Requirements".

Design and fabrication of structural steel, as defined in the AISC Code of Standard Practice, shall conform to the requirements of this Section, and all applicable requirements of the AISC Manual of Steel Construction, latest edition unless otherwise indicated. The Work shall include the following:

§            Designing, furnishing, fabricating and delivering structural steel and crane rails including floor loading signs.

§            Designing, furnishing, fabricating and delivering gallery and auxiliary steel.

§            Designing and furnishing shop and field connections included in the structural, steel.

§        Verifying field measurements for fabrication as required.

INTENT OF SPECIFICATION


The work covered by the specification shall include full provision for the following:

All structural steel, columns, girders, beams, bracing, base plates, column anchor bolts, trolley beams and other materials as required for the support of the buildings, structures, ducts, equipment, piping and other appurtenances above the foundations at grade.

With respect to drawings included in the bid of the offer Document, the following terms shall be clearly understood:

Work indicated on those drawings shall be used only as a guide for the type of steel work which will be required for the Work; actual sizes, weights, thickness, relative quantities of various classes etc. shall be based on Contractor's detailed design drawings.

Cost incurred as a result of changes due to Contractor's design need, misinterpretation of design intent, miscalculation of connections or other design, detailing and fabrication errors shall be Contractor responsibility.

CODES AND STANDARDS

The Contractor shall comply with the requirements of Book II, Subsection 'Codes and Standards'.

The codes and standards of the following organizations extracted from Book II, Subsection 'Codes and Standards' are specifically applicable to the design, manufacture and testing of the work included in this Specification:

AISC     ……….    American Institute of Steel Construction
ANSI     ……….    American National Standards Institute
AREA   ……….    American Railway Engineering Association
ASTM  ………..    American Society for Testing and Materials
AWS    ………..    American Welding society
SSPC  …………   Steel Structures Painting Council, USA
UBC    ..……….   Uniform Building Code of USA


REPORTS AND CERTIFICATES

Copies of material certifications, mill test reports, and other reports required by applicable codes or standards shall be available from the Contractor. Those reports shall be submitted as requested by the Owner after completion of the required tests.


MATERIALS

-All materials for the power plant buildings and other structures shall conform to the requirements of the Contractor's design drawings, Table 4.4.2.14 ‑1 and 4.4.2.14 ‑2 or approved equal.

-Hot rolled steel of wide flange shapes with 600 min or less depth shall be of local origin as long as available.
 
Table 4.4.2.14‑1 MATERIAL FOR STRUCTURAL STEEL WORK


Item
No.
Material
ASTM Standards
Codes Unless Noted
1.
Hot rolled beams, bars, channels, plates
and angles, bracing, structural tees
A36

2.

Plate girders
A36


A572 Grade 50


A588 Grade 50


A588 Grade 46


A588 Grade 42

3.
Columns

A36 or A572 or A588

4.
Cover plates

A36 or
A572 Grade 50
A588 Grade 50

5.
Column base plates and splice plates


A36

6.
Connection bolts

A325F

7.
Welding

AWS D 1.1

8.
Column anchor bolt

A36 or
A307 or
A193 Grade B7
9.
Round tubular bracing

A53
10.
Square and rectangular tubing

A500, Grade B or A501

11.
Castings

A27, Grade 65-35 or
A148, Grade 80-50

12.

Forgings

A668, Classes C, E and F

13
Crane rails
BS 11 or equivalent
   
Note: For additional requirements for material see Table 4.4.2.14‑2

Table 4.4.2.14‑2 ADDITIONAL REQUIREMENTS FOR STRUCTURAL STEEL MATERIALS

Material Item
Standard

Additional Requirements


1. Structural

ASTM A36

Use for- all structural steel other than steels specifically indicated in this


specification

2. High-Strength

a.  ASTM A572

Grade, as required.
    Steel

b.  ASTM A588
Use yield as required.

3. Low-Sulfur
High-Strength Steel (for plates over 12 mm in thickness)
ASTM A588 Grade
a. The sulfur content of the steel shall be 0.010% maximum, and the sulfides shall be in globular forms.

A or B A572 Grade
b.The steel shall have the following properties in through thickness direction:


50 with special process (such as vacuum degassing)
b1.  Reduction of area under tensile test shall be 25% minimum.


b2. The yield and tensile strengths shall be not less than 75% of specified strengths of original A588 or A572. For plates thicker than 56 mm, yield tests shall be performed with test specimens conforming to ASTM A370 Figure 5 for 12 mm dia specimens.



c. The steel shall be 100% ultrasonically


tested, per ASTM A578 Level I for plate thickness of 19 mm and greater, and level 11 for plate thickness less than 19 mm, except that a 25 mm dia. Circle shall be used instead of 75 mm dia. Circle, and scanning shall be continued over 100% of the plate surface.





d. The steel shall be tested for Charpy
    V- Notch Impact, in accordance with


    ASTM   A370 with frequency (P)
    indicated in ASTM A637; and shall  meet the following requirement:






  
 Direction               Charpy Value
                          (Mils-lateral expansion)
                                   At 00C


 Longitudinal                 70
 Transverse                  60
Through-Thickness     30








e. Use: Where indicated, especially for plates loaded or stressed in through thickness direction.

4 Stainless Steel Hot rolled, annealed and pickled (HRAP) finish



a.  ASTM A240,
b.  ASTM A240, conforming to A358, Class 1, Grade 304

Plates
Plates for fabrication of welded plate piping included in structural steelwork.


5. Stainless-Clad Steel, with finish, RMS values of 10 to 30

ASTM A240, Type 304 stainless cladding steel on backing plate of ASTM A36 steel, Conforming to ASTM
 
 Thickness of cladding shall be nominal 1.2 mm single clad for backing plates 6 mm or more in thickness.



6. Tubular  members
6.1Round tubular
     Bracing














ASTM A53 of the following type and grade:
a.  Type E or S, open hearth or basic oxygen steel only, with sculpure Content not exceeding 0.05%

b.  Grade B only (2,460 kg/cm2 yield)


Use standard, extra strong or double extra strong weight.
6.2Rectangular or Square Tubing
  ASTM A500  Grade B or A501
For tubular framing








Table 4.4.2.14‑2 ADDITIONAL REQUIREMENTS FOR STRUCTURAL STEEL MATERIALS (CONT’D)

Material Item
Standard
Additional Requirements

7.High-Strength Bolts

AISC Specification for Structural Joints Using ASTM A325

a. Bolts and Nuts: Use the following materials unless otherwise indicated
a.I. For bolts sizes use A325,Type.1 steel.


      


b.    Washer:


       A325 Bolts: One washer under the head or   or nut whichever is the element turned in tightening.
8 Shoulder bolts for slotted sliding connection.



8.1 Bolts

ASTM A325, Type 1

22 mm diameter shank; grip length of


bolt shall equal the thickness of the mated parts plus two 3 mm thick washers plus 3 mm. Bolt threads shall be 19 mm diameter and the length shall equal the thickness of two nuts plus 6 mm.

8.3 Washers
ASTM F436
Two 22 mm diameter washers required.


One washer under the bolt head and one under the nut.

9.   Castings
a. ASTM A27, Grade
Use for all castings unless otherwise

    65-35.
indicated.


b. ASTM A148, Grade
Use only where high strength steel

    80-50.
castings are required.

10. Forgings
ASTM A688, Classes C, E and F
Use for all forgings unless otherwise indicated.



11. Stock Material
As specified in Items 1
Mill test reports for applicable material

through 10
shall ordinarily constitute sufficient


record, but separate tests may be


required on pieces selected from any







shipment.






Table 4.4.2.14 ‑2 ADDITIONAL REQUIREMENTS FOR STRUCTURAL STEEL MATERIALS (CONT’D)

Material Item
Standard
Additional Requirements

12.    Crane Rails-weight 50 Kg/m or more. (Lighter rails shall conform to manufacturer standards).

ASTM A1, No. 1, Rails with carbon content 0.67-0.82% or manufactures standards meeting the same required

a.      Product: Shall be control cooled and heat treated or end hardened, as made by one of the following manufactures or approved equal in accordance with their standard specification for crane rails, unless otherwise indicated:

a.1. Bethlehem Steel Corporation, USA

a.2. United States Steel Corporation

b.      Length: Standard 12 m, subject tolerance of ASTM A1.

c.      Size: As indicated on the design drawings.

d.      End Drilling: Three holes each end, spaced to suit specified joint bars and as required for tight end joints.

e.      Marking: As specified in ASTM A1.


13.    Crane Rail Accessories

As indicated

Accessories shall be as made by, or as furnished by, one of the rail manufacturers indicated in item 12 in accordance with their standard specifications for rail accessories, for the specified rails and in accordance with the requirements of this Item 13.

13.1   Joint Bars






13.2   Bolts and Nuts


13.3  Spring Washers



ASTM A3






ASTM B325 and
ANSI B18.2

AREA Specification
For spring washers.


Low-carbon steel, with 6 holes and with size and shape of bars and spacing of holes as required for tight end joints
Heat-treated, with finished hexagon heads in accordance with ANSI B 18.2
Alloy steel with one washer for each bolt.


Table 4.4.2.14 ‑2 ADDITIONAL REQUIREMENT FOR STRUCTURAL STEEL MATERIALS (CONT'D)

Material Item
Standard
Additional Requirements

13.4 Rail Clips

ASTM A36 or better

Shall be "Tight Fit" type, made of pressed steel plate with reversible steel fillers and 2 holes each clip.


Also it shall be designed to allow for the


resilient pad and lateral adjustment of the crane rail of ± 5 mm relative to the crane girder, during and after installation.



13.5 Resilient Pad

The resilient pad under the crane rails shall be manufactured  from synthetic elastomer and be resistant –o wear, shear, crushing, oil, grease, oxygen and ultra violet rays and shall be reinforced along its length with a steel strip.





DESIGN

GENERAL PROVISIONS

The design of all structural steel required by this Contract and the design work for all shop and field connections, including angles, welds, web reinforcement for coped beams, gusset plates and bolts shall be performed by Contractor. The Owner prior to fabrication shall submit the design and shop drawings including typical calculations for each connection type for review. Such review shall in no way be interpreted as constituting approval of the adequacy of such design for their intended use and shall not relieve Contractor of correctness and of complete design responsibility and from fulfilling all obligations under the Contract.

All design calculations and drawings shall be prepared under the supervision of a qualified Engineer.

DESIGN REQUIREMENTS

The design of structural steel shall conform to all applicable requirements of the AISC Manual of Steel Construction, latest edition and also conform to the requirements of the following specifications:

"Structural Descriptions and Criteria" Book IIIA, Section 4.4.3

"Welding in Steel Structures" Book IIIA,  Section 4.4.2.20


"Erection of Structural Steel" Book IIIA, Specification 4.4.2.15

The connections shall be designed to resist ultimate moments, shears and axial forces of connected members.

Prying action shall be considered in the design of bolted connection‑s in accordance with the AISC Manual of Steel Construction.

The following allowable stresses specified in the AISC Specification for Structural Joints Using ASTM A325 bolts shall be used in connection bolt
design:

Allowable stresses for blast‑cleaned surfaces (for shop welded and field bolted connections).

Allowable stresses for mill scale surfaces (for shop bolted and field bolted connections).


FABRICATION

GENERAL PROVISIONS

Conformance

Fabrication of structural steel shall conform to all applicable requirements of codes and standards and other standard specifications specified this section, and to all requirements.

FABRICATION REQUIREMENTS FOR PLUMBING UP AND LEVELLING

The structures shall be plumbed and leveled such that deviations in the completed work do not exceed the requirements of the AISC Code of Standard Practice.

These requirements shall be fully considered in fabrication, and Contractor's shop erection drawings shall be clearly marked with these restrictions.

MISFITS

Attention is specifically directed to the requirements of the AISC Code of Standard Practice and Quality Criteria and Inspection Standards, with respect to correction of fabrication errors. Any errors in shop work which prevent proper field assembly (and fit up will be reported, as soon as they are discovered to the Owner and to the fabricator by the Contractor. The Contractor shall then make immediate substitutes or arrange for correction at no cost to the Owner.

The allowable limits for reaming the connection bolt holes for fit up in the shop or in the field shall conform to the requirements of the AISC Quality Criteria and Inspection Standards. If fit up of bolts during erection in the field cannot be           obtained by reaming the fabricated bolt holes within these limits, it is considered that there are errors in fabrication, and these errors shall be rectified in accordance with previous paragraph.

CONNECTIONS

All connections shall be welded or high strength bolted, in the shop or field as follows:

Shop Connections
All members and details shall be fabricated by welding or high strength bolting, using FRICTION TYPE connections; and welding may be used in combination with the high strength bolting completed prior to welding.

The Contractor shall submit with his bid proposal, a schedule of where he proposes to use each method of fabrication, and in general the members, connections, etc. Included under each method.

Field Connections
                          
All connections shall be made with high‑strength bolts, using FRICTION TYPE connections, unless otherwise indicated.

Welding

Conformance

Welding, including stud welding, shall conform to the requirements of Specification refers to "Welding in Steel Structures"

Welding Drawing

All welding shall be clearly indicated on the shop drawings.

Field Welding Preparations

Contractor shall provide all end and edge preparations for field welding.

High Strength Bolting

Conformance

High strength bolting shall conform to the applicable requirements of the AISC Specification for Structural Joints Using ASTM A325 Bolts for friction type connections, and to the requirements of this Clause. Unless otherwise indicated.

Bolt Types

Shall be as indicated in Table 4.4.2.14 ‑2.

Bolt Holes

Shall be 1.5 mm larger than the nominal diameter of the bolt. Larger or slotted holes will not be permitted unless otherwise indicated.

Long Grips

Additional high‑strength bolts are not required for long grips.

Installations

a.The turn‑of‑nut tightening or calibrated wrench tightening methods, as specified in the AISC Specification for Structural Joints Using ASTM A325 Bolts, shall be used. The use of a direct tension indicator for tightening will not be permitted.

b.The minimum projection of the installed bolt beyond the nut shall be 6 mm.

cThe threaded part of the installed bolt shall not be in the shear plane.

d.Blouse of torque bolts will not be permitted.

Beam Connections

Connection Types

Shall conform to the AISC Specification, Part 4.

Connection Angles

a.                                        Connection angles shall be minimum 10 mm thick.

b.                                        Connection angles for any deep girder shall be continuous from the top flange to the bottom flange in all cases.

c.                                        Usual gauge as presented by AISC shall be used. Bolt staggering shall be used only to maintain the usual gauge.

Knife Connection                                                   

This connection, consisting of two-connection angles shop assembled to receive the web of a beam in field erection, shall not be used.


MISCELLANEOUS DETAILS

Welded Cover Plates on Columns and Girders

Cover plates on each flange of columns or girders shall be a single plate in each thickness.

Bracing

Vertical diagonal bracing members shall be wide flange shapes, double angles, double channels or tubular. Horizontal bracing shall be single angles.

Tubular Bracing

a.                              Tubular bracing used for indoor work (not exposed to the elements) shall be open‑ended.
b.                              Tubular bracing used for exterior work (exposed to the elements) shall have the top end capped and the bottom end open. Cap plates shall be 6 mm thick and continuously welded all around the bracing.

Draw for Single-Angle Cross Bracing

Long single angle cross bracing members shall be fabricated with a draw or reduction in the actual distance center to center of end connection bolt holes (as compared to the theoretically correct distance) as indicated in following Table 4.4.2.14 -3; no draw shall be provided for double angle, tubular or other shape bracing:


                           Table 4.4.2.14 -3 DRAW REQUIREMENTS FOR SINGLE ANGLE BRACING


Length
Draw

0 To 3.5 m

Over 3.5 m to 7 m

Over 7 m to 10 m

Over 10 m

-

1.5 mm

3 mm

4.5 mm


Double Angle Bracing

All double-angle bracing members have long legs back-to-back unless otherwise required. 

Camber

Built-up girders, trusses and rolled beams shall be fabricated to provided for camber in accordance with the requirements of the AISC Manual of Steel Construction.

Column Splice Milled Ends

These ends shall not be out of square more than 0.75 mm, as specified in ASTM A6 Table 24. However, only milling techniques shall be used in this fabrication.

Curb Angles and Guard Plates

Connect curb angles and guard plates to the structural steel in the shop.
                 
Guard plates shall be furnished in as large lengths as possible, with joints not closer than 90 cm to handrail posts. Cutouts where required to clear indicate piping, or other equipment, etc., shall be provided.

For adjoining guard in continuous runs or at corners, the ends shall be tack-welded together at the top.

Frames for Removable Concrete Slabs

Angle frames shall be furnished for removable concrete slabs supported on structural steel framing. Contractor will provide lifting inserts for these slabs. Angles shall have headed studs for sound anchorage in concrete.

Hangers
All hangers shall have a minimum of two high-strength bolts at each end.

Trolley Beam Stops

Each trolley beam stop shall consist of two 75 mm x 75 mm x 12 mm angles, each of which shall be connected to the beam with two 18 mm diameter machine bolts. Each bolt shall have hexagon head and one heavy hexagon nut.

Girts

Extent

Girt shall include horizontal girt, carrier girt, girt posts, door and window framing attached to girt, parapet framing, sag rods etc.

Plumb and Level

Girt shall be fabricated to the same plumb and level requirements as specified in paragraph above.

Frames Around Openings

Girt around doors, windows, and louver openings shall be fabricated in accordance with the following requirements:

a.  All corners of openings formed by junctions of vertical and horizontal girt members shall be absolutely square.

b.  Vertical and horizontal dimensions of openings shall each be within an overall tolerance of ± 1,5 mm for doors, ± 6 mm for windows, and + 6 mm, to 0 mm for louvers.

c.   The junctions of vertical and horizontal girt members at the head arid sill of door openings shall be detailed with end clearances not exceeding 6 mm nor less than 3 mm, and shall be arranged for field welding closured, of these junctions.

d. Head angles for windows shall be detailed with end clearances not exceeding 6 mm, nor less than 3 mm; these clearances shall apply for intermediate joints in continuous runs of head angles, and also for joints of junctions of the head angle and jamb angle.  Also, these joints shall be detailed for field welding closures.

e. Fill plates at the junction of jamb angles and sill angles shall be provided, and shall be detailed for field welding closures of these junctions.

f. Steel channel doorframes may be shipped knocked-down for field-welded assembly or may be completely shop-assembled and shipped as a unit.

Connections

Each connection for a girt shall have a minimum of two 16 mm diameter high-strength bolts unless otherwise indicated.

Sag Rods

All sag rods shall have two heavy hexagon nuts each end.  Holes for sag rods shall be 1.5 mm larger than the nominal diameter of the sag rods. Larger holes up to 4,5 mm larger than the road diameter will be permitted only if a hardened washer is used with each nut on each side of these holes.
                          
Stainless-Clad Steel

Edge Preparation and Welding

a. Prior to fabrication, The Contractor shall consult with the manufacturer to ensure the best possible fabrication of the material for the intended purpose. All joints shall be of welded construction unless otherwise indicated and the welding shall be done on both the stainless-clad and backing sides.


b. Only electrodes recommended by the manufacturer for stainless clad steel shall be used for all welding on the stainless clad side of the material. The stainless steel side shall be back gauged or ground to bright sound metal prior to welding. All welding operations shall be performed so as to reduce to a minimum, or completely eliminate, all weld spatters on the stainless-clad side. Also use anti spatter compound along both edges of welded joints, on the stainless-clad side, to permit easier removal of any spatter that does occur, hard, brittle weld is not acceptable.

c.  Grinding of welds will not be required except as necessary to remove sharp edges; however, all welds shall be made as neatly as possible. Pits, crevices and other discontinuities shall be corrected by the use of additional weld metal if required.

Protection

a. The manufacturers shall ship the material in bundles suitable for handling, with wood laths separating each plate.  Wrap each group of plates that make up a bundle shall be completely wrapped in heavy waterproof Kraft paper and steel banded for shipment.

b. Upon receipt of material, leave the plates packaged until the plates are required for fabrication.

Special Precautions

a. Any temporary materials, such as handles of lifting lugs etc. shall not be attached to the stainless-clad side of material.

b. Any scratches, gouges or damages to stainless-clad surfaces shall be satisfactorily by the Contractor at his own expense. Gouges and scratches 0.75 mm deep or less and; those deeper than 0,75 mm fill with weld metal, as specified for welding of stainless-clad steel, and shall be ground and hand-buffed smooth. Weld spatter or other deposits on surfaces shall be carefully removed flush with the surfaces, and these areas shall be hand-buff these areas smooth.

Inspection

Inspect all stainless-clad material shall be inspected, after completion of fabrication, by the Contractor, or by a testing laboratory inspector furnished the by Contractor, for full compliance with all requirements herein specified.  Any work not conforming to specified requirements shall be satisfactorily repaired, before the material is shipped.
Crane-Rails

Rail lengths shall be fabricated so that rail joints on opposite sides of the runway are staggered with respect to each other. Rail joints shall not coincide with the joints occurring in the runway support girders.

Rail shall be milled or grind rails to provide tight joint assembly.

Rail clips shall be tight fit type rail clips in pairs spaced at 60 cm on centers.

SHOP CLEANING AND PAINTING

Shop cleaning and painting including surface preparation of structural steel shall conform to all applicable requirements of specification refers to ''Prime Cost and Shop Painting, and Field Painting".

All trolley beam surface shall be painted yellow with one shop prime coat of paint. The design capacity of each trolley beam shall be stenciled on both sides of the web at the approximate mid span of each beam, using the notation “CAPACITY TONS” lettered in 75 mm high block letters, with black paint. The surface preparation, painting and paint product/manufacturers shall conform to the applicable requirements of Design and Fabrication of structural steel.

Correction of Painting Work

Painted surfaces of structural steel will be inspected, as specified in specification refers to “Prime Coat and Shop Finish Painting” in the field after a reasonable period of weathering. If the condition of any surface indicates insufficient thickness of paint was used, or method of application was incorrect, etc. (regardless of prior approval of the work in the shop), Contractor shall repaint all such surface in the field as requested.

The foregoing requirement shall not apply with respect to surfaces abraded in shipping, handling etc. for which field touchup painting will be performed by the Contractor.


QUALITY ASSURANCE/QUALITY CONTROL (QA/QC)

The quality control procedures so specified shall include but not be limited to the following:

-    Material certificates
-    Welding
-    Non distributive testing
-    Shop test and inspection procedures
-    Cleaning and painting
-    Packaging and shipping

The Quality Control documentation as specified above shall include but not be limited to the following:

-    Material certificates
-    Welding procedures
-    Shop test and inspection reports

INSPECTION AND TEST AT SHOP
The Contractor shall submit a work inspection and test program covering all materials and equipment to the Owner.  Agreement is to be established on the degree of inspection and test to be witnessed by the Owner or his representative before start and during the course of work.

Artikel Terkait